Two Piece Tank (CM Range) Description
Decca Two Piece horizontally split tanks can be manufactured in both standard and custom made versions. These tanks are used where access is restricted and the majority are designed to pass through standard door-ways. Assembly is straight forward, our tank installation teams are also on hand if required.
-
Base Supports
Tanks should be situated on a continuous solid base i.e. marine plywood, TG board, concrete and not rely on cross bracing alone.
-
Man-ways & Inspection
Man-ways are bolted & vented supplied in a standard size of: 600 x 600mm. They can be alternatively supplied hinged as a Deluxe Man-way Inspection hatches 450 x 450mm are supplied standard with tank(s) holding over 1000 litres.
-
Raised Ball Valve Chamber
Standard Ball Valve Chambers are fitted with a reinforced Ball Valve Area(s). These chambers can be pre-insulated. Connection holes may be cut with conventional tools. Holes must be a snug fit.
-
Overflow screens
Each tank is supplied with a DECCA screened overflow to (BS 6700) and tanks supplied to the requirements of Bye-law 30 are complete with a 25mm DECCAscreen tell tale/warning overflow having a 0.65mm micro-mesh filter.
-
Catchment Trays
Readily available on request these items can also be made in sections dependent on the size of unit being supplied.
Typical Properties |
Specific Gravity |
1.5 |
Tensile Strength |
110 MPa |
Tensile Modulus |
7.5 GPa |
Water Absorption |
0.2% |
Thermal Conductivity |
0.2 W/M DEG °C |
Maximum Working Temperature |
60 DEG °C |
-
Covers
Tanks can be supplied with loose fitting covers. In circumstances where Bye-law 30 requirements are specified, the gasketed cover would be fitted with the appropriate screened vent. Access can be arranged as required.
-
Insulation
Tanks can be integrally insulated with Rigid Polyurethane Foam encapsulated in GRP. Thus, protecting and preventing future removal and damage. This is available in several thickness giving corresponding U valves. Alternatively we also stock a 60mm lagging set.